A fault in a recently installed cable at the Canefield Substation has been identified as a key cause of the blackout last weekend that left sections of East Berbice without electricity for about 46 hours.

The Guyana Power and Light Inc. (GPL), in a release today, said the outage began around 8:14 p.m. on Thursday, November 19, when the T2 13.8 kV incomer tripped, resulting in the loss of all circuits at the substation.

Over the following two days, technical teams carried out extensive testing and repairs after discovering several equipment abnormalities. These included deteriorated components, condensation in switchgear, insulation issues and a damaged auxiliary transformer.

However, repeated attempts to energise the system continued to result in tripping.

A major breakthrough came around 3:30 p.m. on Saturday when technicians observed arcing beneath covers over a recently installed 500 mm² cable.

Subsequent testing found that the cable’s B-phase was defective and had short-circuited to ground.

GPL then tested the previously installed 400 mm² cable, found it suitable for use and reconnected it to the system.

By 6:25 p.m. Saturday, the bus was successfully re-energised, allowing the phased restoration of electricity to affected customers to begin.